Hot-water buffer tanks: how much heat can be shifted in time?
Volume and the usable temperature range determine stored energy.
Energy in water
An approximate calculation is the volume in litres multiplied by the temperature difference and by 0.001163 kWh per litre per kelvin. One thousand litres with a usable temperature difference of 20°C stores approximately 23.3 kWh of heat before losses. This is not the same as the electricity used to produce that heat.
Usable temperature
Not all stored heat is suitable for every purpose. Low-temperature space heating may use a different range from domestic hot-water preparation. Consider mixing, thermal stratification, heat exchangers and the minimum required temperature.
Purpose of the tank
Hydraulic stabilisation, reducing cycling and shifting demand in time are different objectives. An oversized tank can increase losses and costs; an undersized one cannot deliver the required shift. Define its function first.
Integration with the EMS
Heat production can be scheduled according to solar generation or prices, but within equipment and comfort limits. Higher temperatures may reduce heat-pump efficiency, so more stored heat does not necessarily mean lower costs.